Eaton Electrical
9575H Series General Purpose Open Style Relays
9575H Series General Purpose Open Style Relays
Type AA panel-mounted relays are rated (each pole) 40A up to 300 Vac, 50/60 Hz; 5A at 480/600 Vac, 50/60 Hz and 40A at 28 Vdc.
Standards and Certifications
- UL listed, E1491
- CSA 41729
- CE: EN60947-4-1, EN60947-5-1
Applications
- 9575H Series 3000 relays are ideal for applications when controlling smaller loads, such as single-phase motors.
Relay Specifications
Coil
- Pull-in voltage: 80% DC coils, 85% AC coils of nominal voltage or less at 25ºC
- Dropout voltage: 10% of nominal voltage or more at 25ºC
- Coil resistance: ±10% measured at 25ºC
- Max. DC coil dissipation capability: 4 watts DC continuous at 25ºC
Contacts
- Contact combination: DPDT
- Contact rating each pole (main contacts): Each pole rated 40 amps up to 300 Vac, 50/60 Hz, 5 amps at 480/600 Vac 50/60 Hz, 0.75 PF load. 1-1/2 hp motor load (each pole) at 120–600 Vac, 50/60 Hz. 2 hp motor load at 200–600 Vac, 50/60 Hz only when using both poles to switch both sides of load, 40 amps at 28 Vdc resistive load each pole. NEMA A 600 pilot duty 50/60 Hz
- Additional contact ratings for relays with blowout magnets: 10A at 110 Vdc resistive, 4A at 225 Vdc resistive, 2A at 325 Vdc resistive. For inductive loads, contacts must be derated accordingly.
- Contact material: Silver cadmium oxide, gold flashed. 5/16 in (7.9 mm) diameter standard Dielectric Withstanding Voltage
- Between open contacts: 1500 Vrms
- All other mutually insulated conductive elements: 2200 Vrms
Miscellaneous
- Coil terminals: 6–32 screws
- Contact terminals: 8-–32 screws
- Main base material: Molded phenolic, UL recognized (QMFZ2)
- Weight (DPDT Relay): 11 oz (311 grams) approximately
- Weight (DPDT Relay with auxiliary switch) 14.5 oz (411 grams) approximately
Auxiliary Switch Specifications
- Contact combination: SPDT
- Contact rating: Auxiliary switch rated 10 amps at 125 or 250 Vac, resistive load; 1/4 hp at 125 or 250 Vac, motor load; 0.4 amps at 125 Vdc or 0.20 amps at 250 Vdc, resistive load; 3 amps at 125 Vac lamp load. All AC ratings are 50/60 Hz
- Dielectric withstanding voltage: 500 Vac rms between open contacts, 1500 Vac rms between all other mutually insulated conductive elements
- Terminals: 4–40 round head screws for auxiliary contacts standard
Catalogs
9575H Series Catalog
125.1 kB